The Fronius Primo Gen24 3.6 Plus inverter offers an emergency power solution even for three-phase consumption.
The Fronius GEN24 Plus single-phase hybrid inverter is the ideal heart for private photovoltaic installations. Thanks to the “PV Point”, it offers a basic integrated emergency power supply, or even a complete emergency power solution if a storage battery is connected.
The use of a storage battery enables energy self-sufficiency in terms of electricity, heating, cooling and electric mobility. With the “Full Backup” option, the Fronius GEN24 Plus offers an emergency power solution even for three-phase consumers, such as heat pumps, and thanks to Multi Flow Technology it even allows parallel power flows in the system in emergency mode.
Data Sheet
PRIMO GEN24 PLUS
Input Data
Models
3.0
3.6
4.0
Number of MPP followers
2
DC input voltage range (Udc min – Udc max)
V
65-600
Rated input voltage (Udc,r)
V
400
Commissioning voltage (start Udc)
V
80
MPP voltage range
V
65 – 530
65 – 530
65 – 530
MPPT1
MPPT2
MPPT1
MPPT2
MPPT1
MPPT2
Max input current per MPPT (Idc max.)
A
22
12
22
12
22
12
Maximum input current per MPPT (Idc max)
A
36
19
36
19
36
19
Number of DC entries in the module field
2
2
2
MPPT1
MPPT2
Total
MPPT1
MPPT2
Total
MPPT1
MPPT2
Total
Max DC power
W
3110
3810
4140
Max PV generator output
Wpico
3750
3110
4500
4600
3810
5520
5000
4140
6000
Output Data
Models
3.0
3.6
4.0
Rated AC power (Pac,r)
W
3000
3680
4000
Apparent power
VA
3000
3680
4000
Max output power
VA
3000
3680
4000
220 VCA
230 VCA
220VCA
230 VCA
220VCA
VCA
AC output current nom. (@ 220 / 230V)
A
13,6
13
16,7
16
18,2
17,4
Grid coupling (Uac,r)
V
1~ NPE 220/230 (+20 %/-30 %)
Frequency (frequency range fmin – fmax)
Hz
50/60 (45 – 65)
Nonlinear distortion coefficient
%
< 2
Power factor (cos φac,r)
0,8 - 1 ind. / cap
Models
3.0
3.6
4.0
PV Point Output Data
Rated Output Power PV Point
VA
3000
3600
4000
Coupling to the PV Point network
V
1~ NPE 220/230
Transition time
Seg.
< 35
Models
3.0
3.6
4.0
Output Data Full Backup2
rated output power "Full Backup"
VA
3000
3600
4000
Coupling to the grid "Full Backup
V
1~ NPE 220/230
Transition time
Seg.
< 35
Models
3.0
3.6
4.0
Battery Connection
Number of DC inputs
1
Max input current (Idc max.)
A
22
DC input voltage range (Udc min - Udc max)3
V
150-455
Battery DC connection technology
Quick connectors by pressure of 2.5-10 mm² (1 unit BAT+ and 1 unit BAT-)
Max DC input/output power 4
W
3110
3810
4140
Max load power with AC4 coupling
W
3000
3680
4000
Compatible Batteries 5
BYD Battery-Box Premium HVS/HVM y LG RESU FLEX6
Isc pv = Isc max. ≥ Isc (STC) x 1.25, according to, for example, IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021
The "Full Backup" option is available for Primo GEN24 from 3.0 to 6.0 Plus. For "Full Backup", additional external components are required for network switching. More detailed information can be found in the instruction manual.
The inverter's AC derating occurs with a DC battery input voltage of 419.7V and higher.
Depending on the connected battery.
Depending on country-specific certification and availability 6 Except BYD Battery-Box Premium HVS 10.2, HVS 12.8, HVM 8.3, HVM 22.1 and LG RESU FLEX 17.2
Models
3.0
3.6
4.0
General data
Dimensions (height × width × depth)
mm
530 X 474 X165
Weight (inverter / with packaging)
kg
15,4/19
15,4/19
15,4/19
protection type
IP66
protection class
1
nocturnal consumption
W
< 10
Overvoltage category (DC/AC)7
2/3
investor concept
without transformer
refrigeration
Active Ventilation Technology
Facility
Indoor and outdoor installation
Ambient temperature range
ºC
-40a +60
Permissible air humidity
%
0-100
noise emission
dB (A)
<42
Max altitude
M
4000
DC PV connection technology
Quick connectors by pressure of 2.5-10 mm² (4 units CC+ and 4 units CC-)
AC connection technology
3-pole AC push-in quick connector 2.5-10 mm² 3-pole push-in quick connector for emergency power 1.5-10 mm² PE screw terminals (2 pieces 2.5-16 mm² and 3 pieces 2.5-10mm²)
Certificates and compliance 8
IEC 62109, IEC 62909, AS/NZS 4777.2, CEI 0-21, ABNT BNR 16149 y 16150, IEC 62116, IEC61727, G98/99
Emergency Power Features
"PV Point" o "Full Backup"
Country of manufacture
Austria
Life Cycle Analysis
According to ÖNORM EN ISO 14040 and 14044 (verified by staff of the Fraunhofer IZM Institute)
Models
3.0
3.6
4.0
Performance
Max performance
%
97,6
97,6
97,6
European performance (ηEU)
%
96,8
97,0
97,1
MPP Fitting Performance
%
>99,9
>99,9
>99,9
Models
3.0
3.6
4.0
Safety equipment
DC insulation measurement
Integrated
Overload behavior
Travel to duty point, power limitation
DC disconnector
Integrated
Reverse polarity protection
Integrated
Models
3.0
3.6
4.0
interfaces
WLAN/2 × Ethernet LAN
Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 digital inputs
6 digital inputs/outputs
Wave control receiver interface, power management
Emergency stop (WSD)
Integrated
Datalogger and web server
Integrated
2 × RS485
Modbus RTU SunSpec (from another manufacturer) / Fronius Smart Meter, battery (GEN24 Plus), Fronius Ohmpilot